Control Algorithm Tuning Parameters - Trane IntelliPak I Programming, Troubleshooting Manual

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Programming SETUP
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.

Control Algorithm Tuning Parameters

Press ENTER to Review or Adjust
Note: Contact the Trane Company before making any adjustment
to these settings
1. Pressing the NEXT key will bypass this section.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
88
OA Bypass Damper
2.0 VDC
OA Bypass Damper
10.0 VDC
OA Bypass Damper
DIRECT ACTING
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 2.0 VDC
Possible Values: 0.0 - 10.0 VDC
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 10.0 VDC
Possible Values: 0.0 - 10.0 VDC
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
RT-SVP04F-EN