Temperature Limit Switch Usage For Gas Heat Units - Trane YHC092E Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners precedent -gas/electric
Table of Contents

Advertisement

Temperature Limit Switch Usage for Gas
Heat Units
Units are factory shipped in the down flow discharge
configuration but can be field converted to a horizontal
discharge configuration. Some, but not all units require a
different TCO1 limit switch, which is attached to the
combustion blower motor if horizontal discharge
configuration is used.
Note: The following units require a limit switch change
out for horizontal discharge. The additional limit
switch is shipped attached to the combustion
blower housing: YSC036E**(M,Y),
YSC036E**(H,Z), YSC048E**(H,Z),
YSC048E**(M,Y) belt drive ID motor,
YSC060E**(H,Z) direct drive ID motor,
YHC047E**(L,X), YHC048E/F**(L,X) direct drive ID
motor, YHC060E/F**(L,X) belt drive ID,
Table 3.
TC01 tripping values
TCO1 Tripping
Unit Model
(Standard
Down flow/
Efficiency)
Horizontal
YSC036E**(L,X)-DD
YSC036E**(L,X)-BD
YSC036E**(M,Y)-DD
170F / 190F
YSC036E**(M,Y)-BD
180F / 190F
YSC036E**(H,Z)-DD
170F / 190F
YSC036E**(H,Z)-BD
155F / 190F
YSC048E**(L,X)-DD
YSC048E**(L,X)-BD
YSC048E**(H,Z)-DD
155F / 210F
YSC048E**(M,Y)-BD
170F / 190F
YSC048E**(M,Y)-DD
YSC048E**(H,Z)-BD
155F / 200F
YSC060E**(L, X)
YSC060E**(M,Y)
YSC060E**(H,Z)-DD
170F / 200F
YSC060E**(H,Z)-BD
YSC072F**(M,Y)
YSC072F**(L,X)
YSC072F**(H,Z)
145F / 155F
YSC090F**(L,X)
180F / 200F
YSC090F**(M,Y)
YSC090F**(H,Z)
YSC092F**(L,X)
YSC092F**(M,Y)
YSC092F**(H,Z)
220F /260F
continued on next page
RT-SVX21K-EN
Values
Unit Model
(High Efficiency - 15
SEER)
180F
YHC036E**(L,X)-DD
170F
YHC036E**(L,X)-BD
YHC036E**(M,Y)-DD
YHC036E**(M,Y)-BD
YHC036E**(H,Z)-DD
YHC036E**(H,Z)-BD
180F
YHC048E/F**(L,X)-DD
170F
YHC048E/F**(L,X)-BD
YHC048E/F**(M,Y)-DD
YHC048E/F**(M,Y)-BD
180F
YHC048E/F**(H,Z)-DD
YHC048E/F**(H,Z)-BD
170
YHC060E/F**(L,X)-DD
170F
YHC060E/F**(L,X)-BD
YHC060E/F**(M,Y)-DD
170F
YHC060E/F**(M,Y)-BD
155F
YHC060E/F**(H,Z)-DD
170F
YHC060E/F**(H,Z)-BD
YHC072F**(L,X)
YHC072F**(M,Y)
155F
YHC072F**(H,Z)
155F
YHC092E**(L,X)
225F
YHC092E**(M,Y)
230F
YHC092E**(H,Z)
YHC092F**(L,X)
YHC036E**(M,Y), YHC037E**(M,Y), YHC048E/
F**(M,Y), YHC060E/F**(M,Y) direct drive ID motor,
YHC036E**(H,Z), YHC048E/F**(H,Z) belt drive ID
motor, YHC060E/F**(H,Z), YSC072F**(H,Z),
YSC090F**(L,X), YSC092F**(M,Y),
YSC092E**(H,Z), YSC102F**(H,Z),
YSC120F**(M,Y), YSC120F**(H,Z),
YHC092E**(M,Y),YHC092F**(M,Y),
YHC102E**(M,Y), YHC120E**(L,X),
YHC120E**(H,Z).
If any of the aforementioned units are installed in the down
flow discharge configuration, remove the additional TCO1
limit switch from the combustion blower motor and
discard.
BD= Belt drive ID motor
DD= Direct drive ID motor
TCO1 Tripping
Values
Unit Model
Down flow/
(High Efficiency -
Horizontal
17 Plus)
180F
YHC037**(L,X)
170F
YHC037**(M,Y)
170F / 190F
YHC037**(H,Z)
180F / 190F
YHC047**(L,X)
170F / 190F
YHC047**(M,Y)
155F / 190F
YHC047**(H,Z)
145F / 155F
YHC067**(L,X)
155F
YHC067**(M,Y)
150F / 170F
YHC067**(H,Z)
170F / 180F
220F
220F / 260F
140F
155F / 145F
145F / 170F
170F
190F / 220F
220F / 230F
200F
190F
210F
135F
135F
170F
190F
Installation
TCO1 Tripping
Values
Down flow/
Horizontal
190F
170F / 220F
220F
145F / 155F
170F
220F
140F
170F
170F
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents