Oa Flow Calibration Data Altitude Values & Associated Data - Trane IntelliPak I Programming, Troubleshooting Manual

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Maximum OA Flow at Design Conditions
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
OA Flow Calibration Data
Altitude:
0 Ft.
1. Press the + or - key until the proper value is displayed
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed
OA Flow Calibration Data Altitude Values & Associated Data
ENGLISH
0 ft
500 ft
1000 ft
1500 ft
2000 ft
2500 ft
3000 ft
3500 ft
4000 ft
4500 ft
ENGLISH
5000 ft
5500 ft
6000 ft
6500 ft
7000 ft
7500 ft
8000 ft
8500 ft
9000 ft
9500 ft
10000 ft
RT-SVP04F-EN
XXX CCFM
SI
ENUM CORR FACTOR
0 m
150 m
300 m
450 m
600 m
750 m
900 m
1050 m
1200 m
1350 m
SI
ENUM CORR FACTOR
1500 m
1650 m
1800 m
2000 m
2150 m
2300 m
2450 m
2600 m
2750 m
2900 m
3050 m
System Programming SETUP
Used With: All units with OA
Normalization: Return Fan and units
with Fresh Air Measurement w/DCV
(VCM) installed.
Used With: All units with Fresh Air
Measurement w/DCV (VCM)
installed.
1.00
0.99
0.98
0.97
0.97
0.96
0.95
0.94
0.93
0.92
0.91
0.91
0.90
0.89
0.88
0.87
0.86
0.85
0.85
0.84
0.83
65