Constant Current Source Mode Procedure; Figure 16 - Current Loop Test Connections - Honeywell ST 800 User Manual

Smartline pressure transmitters
Hide thumbs Also See for ST 800:
Table of Contents

Advertisement

3.7.4 Constant Current Source Mode Procedure

1. Refer to Figure 16 for test connections. Verify the integrity of electrical components in the output
current loop.
2. Establish communication with the Transmitter. For these procedures, the values of components in
the current loop are not critical if they support reliable communication between the Transmitter
and the Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
5. Select the desired constant-level Output: 0 %, 100 %, or Other (any between 0 % - 100 %).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the Transmitter in Analog mode, you can observe the output on an externally-
connected meter or on a local meter. In DE mode, you can observe the output on the local
meter or on the Toolkit Monitor display.
7. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
8. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
9. Select Yes to continue. This concludes the Startup procedure.
Page 24
Figure 16 – Current Loop Test Connections
ST 800 SmartLine Pressure Transmitters User's Manual
Revision 10

Advertisement

Table of Contents
loading

Table of Contents