Commands and Responses
5-9-4
Write Protect Level Setting Data
Command
Response
Variable
MRC
SRC
type
"01"
"02"
"C1"
Address
"0000"
Operation/adjustment protection
"0001"
Initial setting/communication protec-
tion
"0002"
Setting change protection
"0100"
Operation/adjustment protection
"0101"
Initial setting/communication protec-
tion
"0102"
Setting change protection
This command writes protect level setting data. For details on protect levels,
refer to 6-3 Setup Level Configuration and Front Panel Keys .
This command can be used in setting area 0 only. If the Temperature Control-
ler is in setting area 1 when the command is received, it returns an error.
Before executing the command, use operation commands to enable writing
and to enter the protect level.
Response code
MRC
SRC
"01"
"02"
"0000"
Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-6 Write to Variable Area .
Bit
No. of
Address
position
elements
"00"
"0001"
Setting data
Section 5-9
Data
Protect level setting data
73