Omron E5ZN Operation Manual page 102

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Variable Area Map
Variable
Address
type
C1
0000
-
0001
0002
0003
1
0004
0005
0006
0007
0008
0009
000A
000B
000C
000D
000E
000F
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
ch
Setting data name
Operation/adjustment
protection
Initial setting/communica-
tion protection
Setting change protection 00000000H (0):
Set point
Alarm value 1
Alarm upper limit value 1 FFFFF831H to 0000270FH (-1999 to 1999)
Alarm lower limit value 1
Alarm value 2
Alarm upper limit value 2 FFFFF831H to 0000270FH (-1999 to 1999)
Alarm lower limit value 2
Alarm value 3
Manual manipulated
value
Heater burnout detection 00000000H to 000001F4H (0.0 to 50.0)
Set point 0
Set point 1
Temperature input offset
value
Upper limit temperature
input offset value
Lower limit temperature
input offset value
Proportional band
Integral time
Derivative time
Cooling coefficient
Dead band
Manual reset value
Heating hysteresis
Cooling hysteresis
00000000H (0):
No restriction at the operation/adjustment
levels
00000001H (1):
Moving to adjustment level is disabled.
00000002H (2):
Only "PV" and "PV/SP" display and change
enabled.
00000003H (3):
Only "PV" and "PV/SP" display enabled.
00000000H (0):
Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level displayed.
00000001H (1):
Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level not displayed.
00000002H (2):
Moving to initial setting/communications set-
ting levels is disabled.
OFF (Setting changes using the E5ZN-SDL
enabled.)
00000001H (1):
ON (Setting changes using the E5ZN-SDL
disabled.)
Lower value of set point limit to upper value of set point limit
FFFFF831H to 0000270FH (-1999 to 1999)
FFFFF831H to 0000270FH (-1999 to 1999)
FFFFF831H to 0000270FH (-1999 to 1999)
FFFFF831H to 0000270FH (-1999 to 1999)
FFFFF831H to 0000270FH (-1999 to 1999)
Standard: FFFFFFCEH to 0000041AH (-5.0 to 105.0)
Heating/cooling: FFFFFBE6H to 0000041AH (-105.0 to 105.0)
Lower value of set point limit to upper value of set point limit
Lower value of set point limit to upper value of set point limit
FFFFF831H to 0000270FH (-199.9 to 999.9)
FFFFF831H to 0000270FH (-199.9 to 999.9)
FFFFF831H to 0000270FH (-199.9 to 999.9)
00000001H to 0000270FH (0.1 to 999.9)
00000000H to 00000F9FH (0 to 3999)
00000000H to 00000F9FH (0 to 3999)
00000001H to 0000270FH (0.01 to 99.99)
FFFFF831H to 0000270FH (-199.9 to 999.9)
00000000H to 000003E8H (0.0 to 100.0)
00000000H to 0000270FH (0.1 to 999.9)
00000000H to 0000270FH (0.1 to 999.9)
Section 5-10
Description
87