Variable Area Map
Variable
Address
type
C3
0000
-
0001
1
0002
0003
0004
-
0005
1
0006
0007
0008
0009
000A
ch
Setting data name
Input type
Scaling upper limit value
Scaling lower limit value
Decimal point position
Temperature units
Set point upper limit
value
Set point lower limit value Temperature: Input range lower limit to set point upper limit - 1
PID/OnOff
Heating control period
Cooling control period
Direct/reverse operation
Platinum-resistance thermometer input type:
00000000H (0): Pt (-200 to 850°C or -300 to 1,500°F)
00000001H (1): Pt (-199.9 to 500.0°C or -199.9 to 900.0°F)
00000002H (2): Pt (0.0 to 100°C or 0.0 to 210.0°F)
00000003H (3): JPt (-199.9 to 500.0°C or -199.9 to 900.0°F)
00000004H (4): JPt (0.0 to 100.0°C or 0.0 to 210.0°F)
Thermocouple input type:
00000000H (0): K (-200 to 1,300°C or -300 to 2,300°F)
00000001H (1): K (-20.0 to 500.0°C or 0.0 to 900.0°F)
00000002H (2): J (-100 to 850°C or -100 to 1,500°F)
00000003H (3): J (-20.0 to 400.0°C or 0.0 to 750.0°F)
00000004H (4): T (-200 to 400°C or -300 to 700°F)
00000005H (5): E (0 to 600°C or 0 to 1,100°F)
00000006H (6): L (-100 to 850°C or -100 to 1,500°F)
00000007H (7): U (-200 to 400°C or -300 to 700°F)
00000008H (8): N (-200 to 1,300°C or -300 to 2,300°F)
00000009H (9): R (0 to 1,700°C or 0 to 3,000°F)
0000000AH (10): S (0 to 1,700°C or 0 to 3,000°F)
0000000BH (11): B (100 to 1,800°C or 300 to 3,200°F)
0000000CH (12): Non-contact temperature sensor (K10 to
70°C)
0000000DH (13): Non-contact temperature sensor (K60 to
120°C)
0000000EH (14): Non-contact temperature sensor (K115 to
165°C)
0000000FH (15): Non-contact temperature sensor (K160 to
260°C)
00000010H (16): 0 to 50 mV
00000011H (17): T (-199.9 to 400.0°C or -199.9 to 700.0°F)
00000012H (18): U (-199.9 to 400.0°C or -199.9 to 700.0°F)
Scaling lower limit + 1 to 0000270FH (scaling lower limit + 1 to
9,999)
FFFFF831H to scaling upper limit -1 (-1,999 to scaling upper
limit - 1)
00000000H to 00000001H (0 to 1)
00000000H (0): °C
00000001H (1): °F
Temperature: Set point lower limit + 1 to input range upper limit
Analog: Set point lower limit + 1 to scaling upper limit
Analog: Scaling lower limit to set point upper limit -1
00000000H (0): ON/OFF
00000001H (1): 2-PID control
00000001H to 00000063H (1 to 99)
00000001H to 00000063H (1 to 99)
00000000H (0): Reverse operation
00000001H (1): Direct operation
Section 5-10
Description
89