Run/Stop (R-S); Alarm Value 1 (Al-1), Alarm Value 2 (Al-2), Alarm Value 3 (Al-3) - Omron E5ZN Operation Manual

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Operation Level
Monitoring
See Also
7-3-6
RUN/STOP (r-s
Function
Communications
Example of Use
See Also
7-3-7
Alarm Value 1 (al-1
Alarm Value 2 (al-2
Alarm Value 3 (al-3
Function
Communications
00000000H to 00000226 H (0.0 to 55.0)
When the current exceeds 55.0A in the E5ZN-SDL Setting Display Unit,
"ffff" is displayed.
• Related Parameters
"Heater burnout detection" (adjustment level) (page 122)
"Heater burnout use" (advanced function setting level) (page 140)
r-s)
r-s
r-s
Condition: The RUN/STOP function must not be set for the event input.
This parameter starts and stops operation.
Default is "STOP."
Use the "RUN/STOP" operation command. Refer to page 76 for information.
When run is selected, control is executed. When stop is selected, control is
stopped. When control is stopped, the STOP indicator will be lit.
• This parameter is not displayed when the RUN/STOP function is set to
the event input.
• Related Parameters
"Event input allocation" (advanced function setting level) (page 135)
al-1
al-1
al-1)
al-2)
al-2
al-2
al-3)
al-3
al-3
Condition: The alarm type must not be set to no alarm or upper and lower
limit alarm (alarms 1 and 2 only).
These parameters set the input value "X" in the alarm.
• These parameters are used to set the alarm values for alarm outputs 1 to
3.
• During temperature input, the decimal point position is dependent on the
currently selected sensor, and during analog input it is dependent on the
"decimal point" parameter setting.
Setting
Alarm value 1
Alarm value 2
Alarm value 3
Monitoring range
ch
Variable type
1
C1
2
C1
1
C1
2
C1
1
C1
2
C1
Section 7-3
Unit
A
Address
0004
0104
0007
0107
000A
010A
117