Multi-Sp (Set Point 0 To 1) (M-Sp); Set Point During Sp Ramp (Sp-M); Heater Current Value Monitor (Ct) - Omron E5ZN Operation Manual

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Operation Level
7-3-3
Multi-SP (Set Point 0 to 1) (m-sp
Function
Communications
See Also
7-3-4
Ramp SP Value Monitor (sp-m
Function
Communications
Monitoring
See Also
7-3-5
Heater Current Value Monitor (ct
Function
Communications
116
m-sp)
m-sp
m-sp
Condition: The "multi-SP uses" parameter must be set to ON.
Multi-SP allows you to set up to two set points (SP0 to 1) in the adjustment
level. These can be switched between by operating the keys on the front panel
or by external input signals (event input allocation).
In the parameter, enter set points 0 to 1. Default is 0.
Use the multi-SP operation commands. Refer to page 77 for information.
• If multi-SP cannot be selected using the event input, set the "No. of multi-
SP uses" parameter to 0 and the "multi-SP uses" parameter to ON. This
will enable SP selection.
• SP can be selected using the communications function also.
sp-m)
sp-m
sp-m
Condition: The "SP ramp set value" parameter must not be set to 0.
This parameter monitors the SP while the ramp function is being used.
The ramp function restricts the rate of change in the width of the set point.
The set value is displayed when "SP ramp set value" parameter is set.
When the set point is out of the preset ramp, the set point is matched to the
set point set in the "PV/SP" parameter.
ch
1
C0
2
C0
SP: Set point lower limit to set point upper limit
• Related Parameters
"PV/SP" (operation level) (page 115)
"SP ramp set value" (advanced function setting level) (page 136)
"Set point upper limit" "Set point lower limit" (initial setting level)
(page 130)
Condition: The "HBA used" parameter must be set to "ON."
This parameter measures the heater current value from the CT input used for
detecting heater burnout.
Measures and displays the heater current value.
ch
1
C0
2
C0
Variable type
Monitoring range
ct)
ct ct
Variable type
Section 7-3
Address
0002
0102
EU
Address
0003
0103
Unit