Commands and Responses
5-9-7

Communications Writing

Command
Response
5-9-8

Control Start (RUN)/Control Stop (STOP)

Command
Response
76
Command
Related
MRC
SRC
code
information
"30"
"05"
Related information
"00" or "10"
Communications writing prohibited
"01" or "11"
Communications writing not pro-
hibited
This command enables/disables communications writing.
It rewrites the setting for "communications writing."
If communications writing is disabled, operation commands for parameter
rewriting, RUN/STOP, and other operations will be rejected.
Default is communications writing enabled.
This command can be used for setting area 0 or 1.
MRC
SRC
Response code
"30"
"05"
"0000"
Response code: The code shown above repres5nts normal completion. For
details on the response code, refer to 5-7 Operation Commands .
Command
Related
MRC
SRC
code
information
"30"
"05"
"01"
Related
information
ch
"00"
1
"01"
"10"
2
"11"
This command starts and stops control (RUN/STOP).
This command can be used in either setting area 0 or 1.
MRC
SRC
Response code
"30"
"05"
"0000"
Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands .
Description
Contents
Control
RUN
STOP
RUN
STOP
Section 5-9