Set Point Upper Limit (sl-h
Set Point Lower Limit (sl-l
Function
Communications
Settings
See Also
7-5-5
PID/OnOff (cntl
Function
Communications
130
• Related Parameter
"Input type" (initial setting level) (page 128)
sl-h)
sl-h
sl-h
sl-l)
sl-l
sl-l
• These parameters set the upper and lower limits for the SP setting. The
SP can be set within the range defined by the upper and lower limit set
values in the "set point upper limit" and "set point lower limit" parameters.
If existing SP settings are out of the range, they will be changed to either
the upper or lower limit values (which-ever is closest).
• When the temperature input type and temperature unit are changed, the
set point upper limit and set point lower limit will be changed to the upper
and lower limits of the sensor.
• During temperature input, the decimal point position is dependent on the
currently selected sensor. During analog input, it is dependent on the
"decimal point" parameter setting.
Setting
Set point upper limit value
Set point lower limit value
Setting
Set point
Temperature: Set point lower limit +1 to
upper limit
sensor range upper limit
value
Analog: Set point lower limit + 1 to scal-
ing upper limit
Set point
Temperature: Sensor range lower limit to
lower limit
set point upper limit -1
value
Analog: Scaling lower limit to set point
upper limit - 1
• Related Parameters
"Input type" (initial setting level) (page 128) "°C/°F selection" (initial setting
level) (page 129)
cntl)
cntl
cntl
• This parameter selects 2-PID control or ON/OFF control as the control
system.
• The AT tuning function can be used in 2-PID control.
ch
1
2
ch
1
2
1
2
Settings range
Variable type
C3
C3
Section 7-5
Variable type
Address
C3
0005
C3
0105
C3
0006
C3
0106
Unit
Depends
Input range
on °C/°F
upper limit
selection
EU
Scaling upper
limit
Depends
Input range
on °C/°F
lower limit
selection
EU
Scaling lower
limit
Address
0007
0107