Heater Burnout Detection (Hb) - Omron E5ZN Operation Manual

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Adjustment Level
Communications
Monitoring
See Also
7-4-4
Heater Burnout Detection (hb
Function
Communications
Settings
See Also
122
ch
1
C0
2
C0
00000000H to 00000226 H (0.0 to 55.0)
"ffff" is displayed when 55.0A is exceeded in the E5ZN-SDL Setting Display
Unit.
• Related Parameters
"Heater burnout detection" (adjustment level) (page 122)
"HBA used" (advanced function setting level) (page 140)
hb)
hb hb
Condition: The "HBA used" parameter must be set to "ON".
This parameter sets the current value for the heater burnout alarm output to
become active.
• This parameter outputs the heater burnout alarm when the heater current
value falls below this parameter setting.
• When the set value is 0.0, the heater burnout alarm will be OFF. When the
set value is 50.0, the heater burnout alarm will be ON.
ch
1
C1
2
C1
00000000H to 000001F4H (0.0 to 50.0)
• Related Parameters
"HBA used" (advanced function setting level) (page 140)
"Heater current value monitor" (operation or adjustment level) (page 121)
"Heater burnout latch" (advanced function setting level) (page 140)
"Heater burnout hysteresis" (advanced function setting level) (page 140)
Variable type
Monitoring range
Variable type
Setting range
Section 7-4
Address
0003
0103
A
Address
000C
010C
Unit
Default
A
0.0
Unit