3.3 Parameter Checking and Setting

3.3 Parameter Checking and Setting

The inverter is designed to perform simple variable-speed operation with the factory settings of the
parameters. Set the necessary parameters according to the load and operation specifications. Use the
operation panel (FR-DU04) to set, charge and confirm the parameter values. For full information on the
parameters, refer to "CHAPTER 4 PARAMETERS"(Page 60).

3.3.1 Parameter checking

Pr. 160 "user group read selection" is factory-set to display only the simple mode parameters among the
parameters. Set the following parameters as required.
(1) Pr. 160 "user group read selection"
Parameter
Number
160
Setting details
For the setting method and in-depth explanation, refer to page 137.
Pr. 160 Setting
0
1
10
11
9999
( 2 ) Simple mode parameter list
The following parameters are basic parameters made accessible for reading and writing by setting "9999" in
Pr. 160. For details of their functions, refer to Chapter 4 "PARAMETERS" (page 60).
Parameter
Number
0
Torque boost
1
Maximum frequency
2
Minimum frequency
3
Base frequency
4
Three-speed setting (high speed)
5
Three-speed setting (middle speed)
6
Three-speed setting (low speed)
7
Acceleration time
8
Deceleration time
9
Electronic thermal O/L relay
DC injection brake operation
10
frequency
11
DC injection brake operation time
12
DC injection brake voltage
13
Starting frequency
14
Load pattern selection
19
Base frequency voltage
52
DU/PU main display data selection
53
PU level display data selection
54
FM terminal function selection
55
Frequency monitoring reference
56
Current monitoring reference
57
Restart coasting time
58
Restart cushion time
Factory Setting
Setting Range
9999
0, 1, 10, 11, 9999
All parameters are made accessible for reading and writing.
Only the parameters registered in user group 1 are made accessible for reading and writing.
Only the parameters registered in user group 2 are made accessible for reading and writing.
Only the parameters registered in user groups 1 and 2 are made accessible for reading and
writing.
Only the simple mode parameters are made accessible for reading and writing. (Factory setting)
Name
Used to compensate for a voltage drop in the low frequency range to improve
motor torque reduction in the low speed range.
Used to set the upper and lower limits of the output frequency.
Used to match the inverter outputs (voltage, frequency) to the motor rating.
Set these parameters when using the terminals to change the running speeds
preset in the parameters.
Used to set the acceleration and deceleration times.
Used to set the current value of the electronic overcurrent protection to protect the
motor from overheat.
Used to adjust the stopping accuracy according to the load.
Used to select the optimum output characteristic that matches the application and
load characteristics.
Used to set the base voltage (e.g. motor's rated voltage).
Used to choose the monitoring and output signals.
Used to set the frequency and current values, which are referenced, for the level
meter.
Used to perform automatic restart operation after instantaneous power failure or
commercial power supply-inverter switchover.
OPERATION/CONTROL
Description
Application
52
3