Operation Mode Selection (Pr. 79) - Mitsubishi FR-F500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

4.2.37 Operation mode selection (Pr. 79)

Pr. 79 "operation mode selection"
Used to select the operation mode of the inverter.
You can choose any of the operation modes: operation using external signals (external operation), operation
from the PU (FR-DU04/FR-PU04) (PU operation), combination of PU operation and external operation
(external/PU combined operation), and computer link operation (when the FR-A5NR option is used).
Parameter
Factory
Number
Setting
79
0
<Setting>
Pr. 79 Setting
External operation mode at power-on
0
PU or external operation can be selected.
1
PU operation mode
2
External operation mode
External/PU combined operation mode 1
Running frequency .....Set from the PU (FR-DU04/FR-PU04) (direct setting,
3
Start signal .................External signal input (terminal STF, STR)
External/PU combined operation mode 2
Running frequency .....External signal input (terminal 2, 4, 1, jog, multi-speed selection)
4
Start signal .................Input from the PU (FR-DU04/FR-PU04) (
Switch-over mode
6
Switch-over between PU operation, external operation and computer link operation (when the communication
option such as the FR-A5NR is used) modes can be done while running.
External operation mode (PU operation interlock)
7
X12 signal ON ............May be switched to PU operation mode (output stop during external operation)
X12 signal OFF ..........Switching to PU operation mode inhibited
Switching to other than external operation mode (disallowed during operation)
8
X16 signal ON ...........Switched to external operation mode
X16 signal OFF ..........Switched to PU operation mode
Note: 1. Either "3" or "4" may be set to select the PU/external combined operation. These settings differ in
starting method.
Setting Range
0 to 4, 6 to 8
Function
signal input (multi-speed setting only)
105
PARAMETERS
Related parameters
Pr. 15 "jog frequency"
Pr. 4 to Pr. 6, Pr. 24 to 27
(multi-speed operation)
Pr. 76 "alarm code output selection"
Pr. 180 to Pr. 186
(input terminal function selection)
key) or external
key,
key)
FWD
REV
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents