Note: 1. The frequency can be varied by RH (acceleration) and RM (deceleration) between 0 and 120Hz.
2. When the acceleration or deceleration signal switches on, the set frequency varies according to
the slope set in Pr. 44 or Pr. 45. The output frequency acceleration/deceleration times are as set
in Pr. 7 and Pr. 8, respectively. Therefore, the longer preset times are used to vary the actual
output frequency.
3. If the start signal (STF or STR) is off, switching on the acceleration (RH) or deceleration (RM)
signal varies the set frequency.
REMARKS
After the clear signal (RL) has turned on, then off, make a restart (turn on the STF signal) more than 1
minute after that. The output frequency at a restart made within 1 minute will be the output frequency (multi-
speed frequency) after the clear signal (RL) has turned off.
Acceleration (RH)
Clear (RL)
Forward rotation (STF)
Power supply
(*1) External operation frequency or PU operation frequency except multi-speed
(*2) Multi-speed frequency
When selecting this function, re-set the maximum frequency according to the machine.
(*2)
ON
ON
ON
ON
ON
1 minute or less
CAUTION
92
PARAMETERS
ON
ON
ON
ON
ON
More than 1 minute
(*1)