1.2 Basic Configuration

1.2 Basic Configuration
1.2.1 Basic configuration
The following devices are required to operate the inverter. Proper peripheral devices must be selected and
correct connections made to ensure proper operation. Incorrect system configuration and connections can
cause the inverter to operate improperly, its life to be reduced considerably, and in the worst case, the
inverter to be damaged.
Please handle the inverter properly in accordance with the information in each section as well as the
precautions and instructions of this manual. (For connections of the peripheral devices, refer to the
corresponding manuals.)
(NFB)
or
(ELB)
(MC)
AC reactor
(FR-BAL)
Ground
Japanese Harmonic Suppression Guideline
The "harmonic suppression guideline for household appliances and general-purpose prod*ucts" was
issued by Ministry of Economy, Trade and Industry (formerly Ministry of International Trade and Industry)
in September, 1994. This guideline applies to the FR-F520-0.75K to 3.7K. By connection of the power
factor improving reactor (FR-BEL or FR-BAL), this product conforms to the "harmonic suppression
technique for transistorized inverters (input current 20A or less)" set forth by the Japan Electrical
Manufactures Association.
DC reactor
(FR-BEL)
Ground
Name
Use the power supply within the permissible
Power supply
power supply specifications of the inverter.
(Refer to page 184.)
Earth leakage
The breaker should be selected with care
circuit breaker
since a large inrush current flows in the
(ELB) or no-fuse
inverter at power on. (Refer to page 37.)
breaker (NFB)
The magnetic contactor need not be
provided. When installed, do not use it to
Magnetic
start or stop the inverter. It might reduce the
contactor
inverter life.
(Refer to page 37.)
The reactors must be used when the power
factor is to be improved or the inverter is
installed near a large power supply system
Reactors
(1000kVA or more and wiring distance
within 10m (32.81feet)). Make selection
carefully.
The inverter life is influenced by ambient
temperature. The ambient temperature
should be as low as possible within the
permissible range.
This must be noted especially when the
inverter is installed in an enclosure.
Inverter
(Refer to page 7.)
Incorrect wiring might lead to inverter
damage. The control signal lines should
be kept away from the main circuit to
protect them from noise.
(Refer to page 9.)
Devices
Do not connect a power capacitor, surge
connected to the
suppressor or radio noise filter to the output
output
side.
To prevent an electric shock, always ground
the motor and inverter.
The ground wiring from the power line of the
Ground
inverter as an induction noise reduction
technique is recommended to be run by
returning it to the ground terminal of the
inverter. (Refer to page 35)
2
OUTLINE
Description
1