( 3 ) Operation procedure
1) Operation procedure for running
Operation pattern
Switch power on.
Set parameters.
Start, inverter operation
Constant-speed operation,
commercial power supply
operation
Deceleration (stop),
inverter operation
2) Signal on-off after parameter setting
MRS
OFF
Power on
(OFF)
At start
OFF ON
(Inverter)
Constant speed
(Commercial
ON
power supply)
Switched to
inverter
operation for
ON
deceleration
(Inverter)
Stop
ON
! Pr. 135 = "1" (inverter's open collector output terminals)
! Pr. 136 = "2.0 s"
! Pr. 137 = "1.0 s" (Set the value equal to or longer than the time
from when MC3 switches on actually until the inverter and
motor are connected. If it is shorter, restart may not function properly.)
! Pr. 57 = "0.5 s"
! Pr. 58 = "0.5 s" (Always set this parameter when commercial power
supply operation is switched to inverter operation.)
CS
STF
MC1
OFF
OFF
OFF ON
(OFF)
(OFF)
(OFF ON)
OFF ON
OFF ON
ON OFF
ON
OFF ON
ON
ON
ON OFF
131
MC2
MC3
OFF
OFF ON
(OFF)
(OFF ON)
ON
OFF
ON
ON
OFF ON
ON OFF
ON
ON OFF
OFF ON
ON
OFF
ON
PARAMETERS
Remarks
External operation mode
(PU operation mode)
After MC3 switches off,
MC2 switches on.
(Motor coasts during this
period.)
Waiting time 2s.
After MC2 switches off,
MC3 switches on.
(Motor coasts during this
period.)
Waiting time 4s.
4