Wiring Of The Control Circuit - Mitsubishi FR-F500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

2.2.3 Wiring of the control circuit

( 1 ) Wiring instructions
1) Terminals SD, SE and 5 are common to the I/O signals and isolated from each other. These common
terminals must not be connected to each other or earthed.
2) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the
main and power circuits (including the 200V relay sequence circuit).
3) The frequency-input signals to the control circuit are micro currents. When contacts are required, use two
or more parallel micro signal contacts or a twin contact to prevent a contact fault.
4) It is recommended to use the cables of 0.75mm
If the cable gauge used is 1.25mm
running or the cables are run improperly, resulting in an operation panel or parameter unit contact fault.
( 2 ) Terminal block layout
Japanese and NA version
In the control circuit of the inverter, the terminals are arranged as shown below:
Terminal screw size: M3.5
Tightening torque: 1.2 N m
EC version
Terminal screw size: M3.5
Tightening torque: 1.2 N m
A
B
SE RUN SU LPF
2
2
or more, the front cover may be lifted when there are many cables
A
B
C
PC
AM 10E
RL
RM
RH
RT
AU STOP MRS RES SD
SE RUN SU
IPF
OL
FU
C
SD
AM 10E
10
2
OL
FU
STOP MRS RES PC STF
18
INSTALLATION AND WIRING
gauge for connection to the control circuit terminals.
10
2
5
4
1
FM
SD STF STR JOG CS
5
4
1
RL
RM
RH
STR JOG CS
RT
AU
FM
SD
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents