Alarm Code Output; Resetting The Inverter - Mitsubishi FR-F500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

5.1.4 Alarm code output

By setting Pr. 76 "alarm code output selection", an alarm definition can be output as a 4-bit digital signal. This
signal is output from the open collector output terminals equipped as standard on the inverter.
Correlations between alarm definitions and alarm codes are as follows.
Operation Panel
Display
(FR-DU04)
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.FIN
E. GF
E.OHT
E.OLT
E.OPT
E.OP1 to E.OP3
E. PE
E.PUE
E.RET
E.LF
E.CPU
E. 6
E. 7

5.1.5 Resetting the inverter

The inverter can be reset by performing any of the following operations. Note that the electronic overcurrent
protection's internal heat calculation value and the number of retries are cleared (erased) by resetting the
inverter.
Operation 1: Using the operation panel (FR-DU04), press the
Operation 2: Switch power off once, then switch it on again.
Operation 3: Switch on the reset signal (RES).
Output Terminal Signal On-Off
SU
IPF
OL
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
1
0
0
1
0
1
1
1
0
1
1
0
1
1
1
1
1
1
1
1
1
(Note) 0: Output transistor OFF, 1: Output transistor ON (common terminal SE)
PROTECTIVE FUNCTIONS
Alarm Code
FU
1
1
0
2
1
3
0
4
1
5
0
6
1
7
0
8
1
9
1
B
0
C
1
D
0
E
0
E
1
F
The alarm output assumes that Pr. 195 setting is "99" (factory setting).
STOP
key to reset the inverter.
RESET
173
Alarm Output (across B-C)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Not provided (Closed) (Provided
when OLT is displayed (Open))
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents