( 2 ) Connection of the conventional BU brake unit (option)
Connect the BU brake unit correctly as shown below. Incorrect connection will damage the inverter.
Note: 1. The wiring distance between the inverter, brake unit and discharge resistor should be within
2m.
If twisted wires are used, the distance should be within 5m (16.40feet).
2. When the transistor in the brake unit fails, the brake transistor bacomes extremely hot and it has
a chance to get fire. Therefore, install a magnetic contactor on the inverter's power supply side to
shut off current in case of failure.
3. For the power supply of 400V class, install a voltage-reducing transformer.
(3) Connection of the FR-HC high power factor converter (option)
When connecting the high power factor converter (FR-HC) to suppress power harmonics, wire as shown
below. Wrong connection will damage the high power factor converter and inverter.
After making sure that the wiring is correct, set "2" in Pr. 30 "regenerative function selection".
R
NFB
Power
supply
NFB
MC
T (Note 3)
Brake unit
HC HB
S
T
MC1 MC2
R4
S4
R4
S4
From FR-HCL02
R3
S3
MC2
External box
MC1
R2
S2
FR-HCL01
R
S
INSTALLATION AND WIRING
Inverter
R L
U
1
S L
V
2
T L
W
3
Remove jumpers.
P +
N –
Discharge resistor
HA
HB
HC
TB
P
PC
OCR
Constant-
voltage
power
-
supply
+
Comparator
BU brake unit
ON
OFF
MC
MC
High power factor converter (FR-HC)
N
P
Y1 or Y2
T4
T4
T3
T2
T
25
Motor
IM
PR
OCR
N
RDY
RSO
SE
R L
S L
T L
SD
RES
X10 (Note 3)
X11 (Note 3)
N –
P +
R1 L
S1 L
Inverter
1
(Note 1)
2
3
11
(Note 1)
21