# PID control
PID actions are performed as set in Pr. 128 to Pr. 134 (PID control). (Refer to page 120)
In this advanced PID control, a voltage input (0 to 5V or 0 to 10V) may also be used as a process value.
Parameter Number
128
PID action selection
# PID forward-reverse action switching function
Use the X24 signal to switch between the forward and reverse actions under the control of the external
signal. Assign the signal X24 to any terminal using any of Pr. 180 to Pr. 186 (input terminal function
selection). (Refer to page 138)
Parameter Number
Input terminal function
180 to 186
selection
At PID reverse action setting (Pr. 128 = 10, 20, 30): Turning on the X24 signal starts a forward action.
At PID forward action setting (Pr. 128 = 11, 21, 31): Turning on the X24 signal starts a reverse action.
# Assign the motor control signals (SLEEP, R01 to R04, RI01 to RI04) to Pr. 190 to Pr. 195 (output terminal
function selection) or assign them to Pr. 320 to Pr. 322 (RA1, RA21, RA3 output selection) using the
inboard option (FR-A5AR). (The functions of the output terminals are positive logic only.) (Refer to page
140)
Parameter Number
190
RUN terminal function selection
191
SU terminal function selection
192
IPF terminal function selection
193
OL terminal function selection
194
FU terminal function selection
320
RA1 output selection (valid only when the FR-A5AR is used)
321
RA2 output selection (valid only when the FR-A5AR is used)
322
RA3 output selection (valid only when the FR-A5AR is used)
Additional Setting
Range
Set value
40, 41, 42, 43, 44, 45,
46, 47, 48
Additional Setting
Name
Additional Setting
Name
Name
Signal name
40
SLEEP
Output at stop
41
R01
Commercial power supply side motor 1 connection R01
42
R02
Commercial power supply side motor 2 connection R02
43
R03
Commercial power supply side motor 3 connection R03
44
R04
Commercial power supply side motor 4 connection R04
45
RI01
Inverter side motor 1 connection RI01
46
RI02
Inverter side motor 2 connection RI02
47
RI03
Inverter side motor 3 connection RI03
48
RI04
Inverter side motor 4 connection RI04
Description
Range
30: PID reverse action
30, 31
31: PID forward action
Description
Range
24
X24 signal
A reverse action is performed when the X24 signal is
off.
A forward action is performed when the X24 signal is
off.
Description
Function
149
PARAMETERS
4