Mounting Method 3
J
Use this method to mount the Digital Operator from the front of the panel using resin parts.
The Digital Operator can be mounted and removed from the panel easily. (To fix the Digital Operator per-
manently, use Sems screws M3 x 8 from the back of the Operator bracket.)
As shown in the following diagram, this method mounts the Digital Operator from the front of the panel
using a resin part on the back of the panel, and by drilling mounting holes and making a cutout in the panel.
When attaching the cable to the resin part, open the cable connector cover fully, and insert the connector
until the cable audibly snaps into place. (If the cable is not securely mounted, the connection with the Digi-
tal Operator will be poor.)
The code number for the metal plate is DACT32183-BD.
Panel cutout
(Viewed from the front of the panel.)
Panel
cutout
4.5 (0.18)
101 (3.98)
110 (4.33)
Fig 14.23
Mounting the Digital Operator to the Panel Method 3 (Unit: mm)
Panel surface
Panel front
2-φ4.8 hole
4.5 (0.18)
14 -57
14.3 Options and Peripheral Units
Mounted on the panel
Resin part
Mount the
cable firmly
Panel back
50 min.