Items Marked "Reset; Items Marked "Detailed Display - Omron WS02-LCTC1-EV5 - V5.2 REV 12-2008 Manual

Table of Contents

Advertisement

Monitor Run Status
1, 2, 3...

4-5-2 ITEMs Marked "Reset"

4-5-3 ITEMs Marked "Detailed display"

Note For a Loop Control Unit, the processing time load rate and maximum control load
rate indication for each operation cycle block (e.g., ITEM 054 and ITEM 055), are
indicated in 0.01% units. The data range is 0.00 to 100.00 (unit: 0.01%). For an
LCBjj, the processing time load rate and maximum control load rate indica-
tion (LCB load rate and maximum load rate) for the overall Loop Controller for
each operation cycle block (e.g., ITEM 047 and ITEM 048), are indicated in1%
units. The data range is 0 to 100 (unit: 1%).
1. The values under the Data column are recorded when the Monitor Run Sta-
tus Dialog Box is opened.
2. To refresh the data with the dialog box displayed, click the Refresh Button.
3. To execute the ITEM displayed under the Run column, select the ITEM and
click the Execute Button.
Example
ITEMs remarked "Reset" can be set to 0 (reset). Select the ITEM and click
the Execute Button. The following dialog box will appear. Click the OK But-
ton.
Example
The details of ITEMs remarked "Detailed display" can be changed through
the Execution Menu.
Example: Minimum block address with an execution error resulted
The error code (i.e., the value stored in ITEM003) for each function block will
be displayed in the block address with the vertical row specifying the 10's
digit in the block address and the horizontal row specifying the 1's digit in the
block address.
–1:
0:
Other (1 to 89): Error (Execution error code)
For details on execution error codes, refer to the Operation Manual for the
Loop Controller, or Function Block Reference Manual.
Example: Minimum block address with an execution error is 002.
Block address not used
Normal (Execution error code)
Section
4-5
267