Initial Settings for Online Connections
Initial Settings in
CX-Process Tool
1, 2, 3...
Setting Unit Addresses
(Loop Control Units
Only)

4-2-5 Connecting with EtherNet/IP

Initial Settings for the
CX-Process Tool
1, 2, 3...
250
• Turn ON pin 5 (or the COMM pin for a CS1D Duplex System) of the DIP Switch
when using the RS-232C port. Also, set the appropriate word in the PLC Setup
(Programming Console address 160) to 0400 Hex.
After completing the steps described above, take the following steps in the CX-
Process Tool.
1. Select Change PLC from the Settings Menu.
2. The Change PLC Dialog Box will be displayed.
Select Toolbus (Peripheral Bus) as the network type.
3. If necessary, the Network Settings Dialog Box can be displayed by clicking
the Settings (S) Button next to the network type.
The port name (COM port number) can be selected in the Driver Tab.
Note When CX-Server has been selected as the communications driver, set the node
address to a non-zero value in the Network Settings Dialog Box before compiling
the Monitor tag file or CSV tag file. Select Change PLC from the Settings Menu
to display the dialog box. (If the computer is connected online, return the node
address setting to 0.)
The unit address setting for the Peripheral Bus connection is the same as the
unit address setting for the serial connection. Refer to Setting Unit Addresses on
page 249 for details.
Perform the following procedure to use EtherNet/IP for the communications pro-
tocol.
1. Select Change PLC from the Setting Menu.
2. The Change PLC Dialog Box will be displayed.
3. Set the network type to EtherNet/IP.
4. In the Network Setting Dialog Box, enter the IP address of the target PLC.
Note When EtherNet/IP is used as the communications protocol, the IP address of the
target PLC will be displayed as shown below. The node display format is as fol-
lows: Node_number [CPU_model/EIP(IP_address)
Section
4-2
The IP address of
node 00 is displayed.