In factory setting, analog voltage of approx. 10 V is output when output
frequency (output current) is 100 %.
Frequency
Meter
AM
AC

Calibrating Frequency Meter or Ammerter (n067)

Used to adjust analog output gain.
Frequency Meter/Ammeter
(3 V 1 mA Full-scale)
n067
Set the analog output voltage at 100 % of output frequency (output cur-
rent). Frequency meter displays 0 to 60 Hz at 0 to 3 V.
n067 setting
10 V ×
Using Analog Output (AM-AC) as a Pulse Train Signal
Output (n065)
Analog output AM-AC can be used as a pulse train output (output fre-
quency monitor, frequency reference monitor).
Set n065 to 1 when using pulse train output.
Constant No.
n065
Monitor Output Type
Output Frequency
(Output Current)
100 %
FM
Output Frequency
(Output Current)
AM
FM
AC
Output frequency becomes
= 3 V
0.30
100 % at this value.
Name
6 Programming Features
Analog monitor gain
can be set by n067.
0
10 V
Analog Output
n067 = 0.30
100 %
0
3 V
10 V
Analog Output
Unit
Setting
range
-
0, 1
n067 = 1.00
Factory Setting
Factory setting
0