Omron VARISPEED V7 User Manual page 207

Varispeed v7 compact sensorless vector inverter
Hide thumbs Also See for VARISPEED V7:
Table of Contents

Advertisement

Fault Display
Digital
RUN (Green)
Operator
ALARM (Red)
206
Inverter
Status
OL1 (Motor overload)
Protective
Operation
Motor overload protection op-
Output is
erated by built-in electronic
turned OFF
thermal overload relay.
and motor
coasts to a
stop.
OL2 (Inverter overload)
Inverter overload protection
operated by built-in electron-
ic thermal overload relay.
Description
Causes and Corrective
Actions
Check the load size or V/f
pattern setting (constants
n011 to n017).
Set the motor rated cur-
rent shown on the name-
plate in constant n036.
Check that the settings of
motor protection (whether
motor cooling method is
self-cooled or fan-cooled)
and motor protection time
constant are made cor-
rectly.
Check the load size, V/f
set value, operation pat-
tern, etc. to confirm that
the load is not excessive
under actual operation.
Recheck the item of
motor protection and set
the constants again if
necessary.
Refer to Carrier Fre-
quency Selection
(n080)14kHz max on
page 94.
Check the wiring
(increase of current
caused by rare shortcir-
cuit, etc.).
Check the load size or V/f
pattern setting (constants
n011 to n017).
Check the Inverter capac-
ity.
Check the load size, V/f
set value, operation pat-
tern, etc. to confirm that
the load is not excessive
under actual operation.
Refer to Carrier Fre-
quency Selection
(n080)14kHz max on
page 94.
Check the wiring
(increase of current
caused by rare shortcir-
cuit, etc.).