n141
PTC Thermistor In-
put Motor Overheat
Protection Selection
n142
Motor Temperature
Input Filter Time
Constant
Note: When the analog signal (0 to 10 V) input into terminal FR is used as the
motor overheat signal for the PTC thermistor input (FR) (when n141 is
set to 1 or higher), the signal cannot be used as a frequency reference or
for PID feedback. (There are restrictions when setting constants.)
The following settings cannot be set from the Digital Operator. (After
the error is displayed on the Digital Operator, the value returns to the
value before the change.)
If the following settings are set from the MEMOBUS, a constant setting
error will occur. (oP7 will flash on the Digital Operator.)
Name
0: No overheat protection with PTC
thermistor input (FR)
1 or higher: Overheat protection with
PTC thermistor input (FR)
Note:
oH8 / oH9 alarm: User can select the
inverter decelerate to a stop or not.
1: Only oH8 alarm, not to a stop.
2: oH8 alarm, and decelerate to a
stop (oH9 fault output).
3: oH8 alarm, and decelerate to a
stop (oH9 fault output) using n022
(Deceleration Time 2) decelera-
tion time
4: oH8 alarm, and coasting to a stop
(oH9 fault output) .
5: not oH8 alarm, and decelerate to
a stop (oH9 fault output).
6: not oH8 alarm, and decelerate to
a stop (oH9 fault output) using
n022 (Deceleration Time 2) decel-
eration time.
7: not oH8 alarm, and coasting to a
stop (oH9 fault output).
Setting Unit: 0.1 s
Setting Range: 0.0 to 10.0 s
6 Programming Features
Description
Fac-
tory
Set-
ting
0
0.2
sec
139