2. Main Circuits
Model
Terminal Symbols
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
20P1
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
20P2
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
20P4
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
20P7
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
21P5
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
22P2
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
24P0
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
25P5
U/T1, V/T2, W/T3
CIMR-
R/L1, S/L2, T/L3, -
V7ΑΖ
, +1, +2, B1, B2,
27P5
U/T1, V/T2, W/T3
Note: The wire size is given for copper wire at 75°C (160°F).
200 V Class 3-phase Input Inverters
Screws
Tightening
Torque
N•m (lb•in)
M3.5
0.8 to 1.0
(7.1 to 8.88)
M3.5
0.8 to 1.0
(7.1 to 8.88)
M3.5
0.8 to 1.0
(7.1 to 8.88)
M3.5
0.8 to 1.0
(7.1 to 8.88)
M4
1.2 to 1.5
(10.65 to 13.31)
M4
1.2 to 1.5
(10.65 to 13.31)
M4
1.2 to 1.5
(10.65 to 13.31)
M5
2.5
(22.13)
M5
2.5
(22.13)
Wires
Applicable Size
Recommended
AWG
2
mm
mm
0.75 to 2
18 to 14
0.75 to 2
18 to 14
0.75 to 2
18 to 14
0.75 to 2
18 to 14
2 to 5.5
14 to 10
2 to 5.5
14 to 10
2 to 5.5
14 to 10
5.5 to 8
10 to 8
5.5 to 8
10 to 8
4 Wiring
Type
Size
AWG
2
2
14
600-V
vinyl-
sheathed
or equiva-
lent
2
14
2
14
2
14
2
14
3.5
12
3.5
12
5.5
10
8
8
8
8