Wiring Instructions
NOTE
1. Always connect the power supply for the main circuit
inputs to the power input terminals R/L1, S/L2, and T/L3
(R/L1, S/L2 for single-phase power) via a molded-case
circuit breaker (MCCB) or a fuse. Never connect the
power supply to terminals U/T1, V/T2, W/T3, B1, B2, −,
+1, or +2. The Inverter may be damaged.
For single-phase Inverters, always use terminals R/L1 and
S/L2. Never connect terminal T/L3. Fuses must be of UL-
class RK5 fuse or an equivalent.
Refer to page 231 for recommended peripheral devices.
Inverter Power Supply Connection Terminals
200-V 3-phase Input
Power Supply Speci-
fication Inverters
CIMR-V7
2
Connect to R/L1,
S/L2, and T/L3.
2. If the wiring distance between Inverter and motor is long,
reduce the Inverter carrier frequency. For details, refer to
Carrier Frequency Selection (n080)14kHz max on page
94.
3. Control wiring must be less than 50 m (164 ft) in length
and must be separated from power wiring. Use shielded
twisted-pair cable when inputting the frequency signal
externally.
4. Only basic insulation to meet the requirements of protec-
tion class 1 and overvoltage category II is provided with
control circuit terminals. Additional insulation may be
necessary in the end product to conform to CE require-
ments.
5. Closed-loop connectors should be used when wiring to the
main circuit terminals.
Delayed response may cause injury or damage the
machine.
200-V Single Input
Power Supply Speci-
fication Inverters
CIMR-V7
Connect to R/L1 and
S/L2.
400-V 3-phase Input
Power Supply Speci-
fication Inverters
B
CIMR-V7
Connect to R/L1,
S/L2, and T/L3.
4 Wiring
4
29