Using Frequency Meter Or Ammeter; Calibrating Frequency Meter Or Ammeter - Omron VS mini J7 User Manual

Compact general purpose inverter
Hide thumbs Also See for VS mini J7:
Table of Contents

Advertisement

Using frequency meter or ammeter (n44)
Selects to output either output frequency or output current to analog output
terminals AM-AC for monitoring.
Setting
Setting
Description
0
Output frequency
1
Output current
In initial setting, analog voltage of approx. 10V is output when output frequency
(output current) is 100%.
FREQUENCY METER
AM
FM
FM
0 TO 10VDC
AC
Calibrating frequency meter or
ammeter (n45)
Used to adjust analog output gain.
FREQUENCY METER/AMMETER
(3V 1mA FULL-SCALE)
AM
n45
AC
Set the analog output voltage at 100% of output frequency (output current).
Frequency meter displays 0 to 60Hz at 0 to 3V.
n45 Setting
10V
0.30
56
OUTPUT FREQUENCY
(OUTPUT CURRENT)
OUTPUT FREQUENCY
(OUTPUT CURRENT)
FM
= 3V
·
·
·
Output frequency becomes
100% at this value.
100%
0
10V
ANALOG OUTPUT
n45=0.30
100%
3V
ANALOG OUTPUT
Analog monitor gain
can be set by n45
FACTORY SETTING
n45=1.00
10V