Troubleshooting Flowcharts - Omron CPM2A - 11-2005 Manual

Programmable controllers
Table of Contents

Advertisement

Troubleshooting Flowcharts

5-5

Troubleshooting Flowcharts

Main Check
Type
Message
B
IL-ILC ERR
IL(02) and ILC(03) are not used in pairs. Check the
program before processing.
JMP-JME ERR
JMP(04) and JME(05) are not used in pairs. Check the
program before processing.
SBN-RET ERR
RET(93) has not been used properly or the relationship
between SBN(92) and RET(93) is not correct. Correct the
program.
C
COIL DUPL
The same bit is being controlled (i.e., turned ON and/or
OFF) by more than one instruction (e.g., OUT, OUT NOT,
DIFU(13), DIFD(14), KEEP(11), SFT(10)). This error
occurs when the same number is used for the timer and
counter instructions. Although this is allowed for certain
instructions, check instruction requirements to confirm that
the program is correct or rewrite the program so that each
bit is controlled by only one instruction.
JMP UNDEFD
JME(05) has been used with no JMP(04) with the same
jump number. Add a JMP(04) with the same number or
delete the JME(05) that is not being used.
SBS UNDEFD
A subroutine exists that is not called by SBS(91). Program
a subroutine call in the proper place, or delete the
subroutine if it is not required.
Use the following flowcharts to troubleshoot errors that occur during operation.
Error
PWR indicator lit?
Yes
RUN indicator lit?
Yes
ERR/ALM indicator
flashing?
Not lit
Is I/O sequence
normal?
Yes
Operating
environment normal?
Yes
Replace the CPU
Unit.
Meaning and appropriate response
No
Check power supply. (See page 134.)
No
Operation stopped. Check for fatal errors.
(See page 135.)
Flashing
Check for non-fatal errors. (See page 136.)
No
Check I/O. (See page 137.)
No
Check operating environment. (See page 139.)
Section
5-5
133