3-1 Installation Notes

For improved reliability and maximized functionality, take the following factors into consideration when
installing a CP1L system.
Installation Location
3
Installation into Cabinets and Control Panels
Temperature Control
30
SYSMAC CP1L/CP1E Introduction Manual
Do not install in the following locations:
• Locations subject to ambient temperature lower than 0° C or higher than
55 °C .
• Locations subject to dramatic temperature changes, causing possible
condensation.
• Locations subject to relative humidity lower than 10%RH or higher than
90%RH.
• Locations subject to corrosive or flammable gases.
• Locations subject to excessive dust, salt, or metal powder.
• Locations subject to shock or vibration.
• Locations exposed to direct sunlight.
• Locations subject to water, oil, or chemical reagent splashes.
Shield the system sufficiently when installing in the following locations:
• Locations subject to static electricity and other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible radioactive exposure.
• Locations in close proximity to close to power lines.
When installing CP1L into a cabinet or control panel, ensure adequate
environment resistance, as well as sufficient accessibility for operation and
maintenance.
The ambient operating temperature for CP1L is 0 to 55 °C . The following
precautions apply.
• Provide adequate space for air flow.
• Do not install above equipment, which generates significant heat (i.e. heaters,
transformers, high-capacity resistors).
• If the ambient temperature is to exceed 55 °C , install a cooling fan or air
conditioner.