CJ1W-IA201 AC Input Unit (200 VAC, 8 Points)

Name
Model
Rated Input Voltage
Rated Input Voltage Range
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Current
ON Response Time
OFF Response Time
Number of Circuits
Number of Simultaneously ON Points
Insulation Resistance
Dielectric Strength
Internal Current Consumption
Weight
Accessories
Circuit Configuration
Terminal Connections
*1 The Input ON and OFF response times for Basic I/O Units can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms,
16 ms, or 32 ms in the PLC Setup. When the response times have been set to 0 ms, the ON response time will
be 10 ms maximum and the OFF response time will be 40 ms maximum due to internal element delays.
*2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also
treated as a 16-point I/O Unit in the I/O tables.
CJ2 CPU Unit Hardware User's Manual
8-point AC Input Unit with Terminal Block
CJ1W-IA201
200 to 240 VAC 50/60 Hz
170 to 264 VAC
21 kΩ (50 Hz), 18 kΩ (60 Hz)
9 mA typical (at 200 VAC, 50 Hz),
11 mA typical (at 200 VAC, 60 Hz)
120 VAC min./4 mA min.
40 VAC max./2 mA max.
18.0 ms max. (PLC Setup default setting: 8 ms)
48.0 ms max. (PLC Setup default setting: 8 ms)
8 (8 points/common, 1 circuit)
100% (8 points/common) simultaneously ON
20 MΩ between external terminals and the GR terminal (500 VDC)
2,000 VAC between the external terminals and the GR terminal for
1 minute at a leakage current of 10 mA max.
80 mA max.
130 g max.
None
Signal
name
Input indicator
820 Ω
1 MΩ
IN0
to
0.15 µF
IN7
220 Ω
COM
*2
Connec-
Signal
tor pin
name
A0
NC
IN0
B0
A1
NC
IN1
B1
A2
NC
IN2
B2
A3
NC
IN3
B3
A4
NC
IN4
B4
A5
NC
IN5
B5
A6
NC
IN6
B6
A7
NC
IN7
B7
NC
A8
COM
B8
Appendices
*1
*1
200 to 240 VAC