CJ1W-OA201 Triac Output Unit (8 Points)

Name
Model
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Number of Circuits
Surge Protector
Fuses
Insulation Resistance
Dielectric Strength
Internal Current Consumption
Weight
Circuit Configuration
Terminal Connections
*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also
treated as a 16-point I/O Unit in the I/O tables.
A-22
8-point Triac Output Unit with Terminal Block
CJ1W-OA201
0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit)
15 A (pulse width: 10 ms max.)
50 mA 75 VAC
1.5 mA (200 VAC) max.
1.6 VAC max.
1 ms max.
1/2 of load frequency + 1 ms or less.
8 (8 points/common, 1 circuit)
C.R Absorber + Surge Absorber
5 A (1/common, 1 used)
The fuse cannot be replaced by the user.
20 MΩ between the external terminals and the GR terminal (500 VDC)
2,000 VAC between the external terminals and the GR terminal for
1 minute at a leakage current of 10 mA max.
220 mA max.
150 g max.
Output indicator
*1
Connec-
Signal
tor pin
name
NC
A0
OUT0
L
B0
NC
A1
OUT1
L
B1
NC
A2
OUT2
L
B2
NC
A3
OUT3
L
B3
NC
OUT4
A4
L
B4
NC
A5
OUT5
L
B5
NC
OUT6
A6
L
B6
NC
A7
OUT7
L
B7
NC
A8
COM
B8
Signal
name
OUT0
to
OUT7
COM
Fuse
250 VAC max.
CJ2 CPU Unit Hardware User's Manual