Cj1W-Od213 Transistor Output Unit (16 Points) - Omron CJ2 CPU UNIT User Manual

Cj2 cpu unit hardware
Hide thumbs Also See for CJ2 CPU UNIT:
Table of Contents

Advertisement

Appendices

CJ1W-OD213 Transistor Output Unit (16 Points)

Name
Model
Rated Voltage
Operating Load Voltage
Range
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption 5 VDC 150 mA max.
Fuse
External Power Supply
Weight
Circuit Configuration
Terminal Connections
*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
A-26
16-point Transistor Output Unit with Terminal Block (Sinking Outputs)
CJ1W-OD213
24 VDC
20.4 to 26.4 VDC
0.5 A/point, 5.0 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
15 µs max.
80 µs max.
20 MΩ between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at
a leakage current of 10 mA max.
16 (16 points/common, 1 circuit)
None
20.4 to 26.4 VDC, 55 mA min.
110 g max.
Output indicator
*1
Signal
Connec-
Signal
tor pin
name
name
OUT0
L
A0
OUT1
L
B0
OUT2
A1
L
OUT3
L
B1
OUT4
A2
L
OUT5
L
B2
OUT6
L
A3
OUT7
L
B3
OUT8
L
A4
OUT9
L
B4
OUT10
L
A5
OUT11
L
B5
OUT12
L
A6
OUT13
L
B6
OUT14
L
A7
OUT15
L
B7
COM
A8
+V
B8
24 VDC
• When wiring, pay careful attention to the polarity of the external power sup-
ply. The load may operate incorrectly if the polarity is reversed.
Signal
name
+V
OUT0
to
OUT15
COM
CJ2 CPU Unit Hardware User's Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents