Fail-Safe Circuits; Order Of Powering Up The Cpu Unit And Controlled System; Managing Cpu Unit Errors; Managing Output Malfunctions - Omron CJ2 CPU UNIT User Manual

Cj2 cpu unit hardware
Hide thumbs Also See for CJ2 CPU UNIT:
Table of Contents

Advertisement

5 Installation
5-1

Fail-safe Circuits

Be sure to set up safety circuits outside of the PLC to prevent dangerous conditions in the event of
errors in the PLC or external power supply.

Order of Powering Up the CPU Unit and Controlled System

Outputs from Units such as DC Output Units may malfunction momentarily when the power to the PLC
is turned ON. This may cause problems in the system if the PLC's power supply is turned ON after the
controlled system's power supply. To prevent possible malfunctions, add an external circuit that pre-
vents the power supply to the controlled system from going ON before the power supply to the PLC
itself.

Managing CPU Unit Errors

When any of the following errors occurs, PLC operation will stop and all outputs from Output Units will
be turned OFF.
• Operation of the Power Supply Unit's overcurrent protection circuit
• A CPU error (watchdog timer error) or CPU on standby
• A fatal error (memory error, Memory Card transfer error, I/O bus error, Unit/Rack number duplication
error, too many I/O points error, I/O setting error, program error, cycle time exceeded error, or
FALS(007) error)
Be sure to add any circuits necessary outside of the PLC to ensure the safety of the system in the event
of an error that stops PLC operation.
*1 When a fatal error occurs, all outputs from Output Units will be turned OFF even if the IOM Hold Bit has been
turned ON to protect the contents of I/O memory. (When the IOM Hold Bit is ON, the outputs will retain their
previous status after the PLC has been switched from RUN/MONITOR mode to PROGRAM mode.)

Managing Output Malfunctions

It is possible for an output to remain ON due to a malfunction in the internal circuitry of the Output Unit,
such as a relay or transistor malfunction. Be sure to add any circuits necessary outside of the PLC to
ensure the safety of the system in the event that an output fails to go OFF.
5-2
*1
CJ2 CPU Unit Hardware User's Manual