3 Nomenclature and Functions

DIP Switch

Pin no.
SW1
Used to prevent programs from being
accidentally overwritten from Program-
ming Devices (including the CX-Program-
mer).
SW2
Set to ON to read the program
(AUTOEXEC.OBJ file) and parameter
area (AUTOEXEC.STD file) from the
Memory Card to the CPU Unit when
power is turned ON.
Used to store the programs in the Mem-
ory Card to switch operations, or to auto-
matically transfer programs at startup
(Memory Card ROM operation).
SW3
Not used.
SW4
Not used.
SW5
Set to ON to automatically detect the
baud rate of the CX-Programmer (periph-
eral bus only) when using the serial port
(RS-232C).
SW6
Set pin 6 to ON or OFF and use A395.12
in the program to create a user-defined
condition without using an Input Unit.
SW7
Set the simple backup type. (Refer to
Table 2 below.)
SW8
---
*1 The following data cannot be overwritten when pin 1 is ON:
• All parts of the user program (programs in all tasks)
• All data in the parameter area (such as the PLC Setup and I/O table)
When pin 1 is ON, the user program and parameter area will not be cleared when the memory clear opera-
tion is performed from a Programming Device.
*2 I/O memory files (AUTOEXEC.IOM and ATEXEC@@.IOM) are automatically transferred when power is turned
ON if pin 2 is set to ON. Both the program (AUTOEXEC.OBJ) and parameter area (AUTOEXEC.STD) files
must be stored on the Memory Card. It is not necessary for the I/O memory files (AUTOEXEC.IOM and
ATEXEC@@.IOM) to be stored on the Memory Card.
*3 When pin 7 is ON, simple backup reading from the Memory Card is given priority, so even if pin 2 is ON, the
user program is not automatically transferred from the Memory Card when power is turned ON.
*4 Connecting to the PLC is not possible from the CX-One Support Software using SYSMAC WAY even if pin 5 on
the DIP switch is OFF and the PLC Setup is set to the Host Link protocol (i.e., the default setting).
*5 With the CJ2M-CPU3@, pin 5 can be set only when a Serial Option Board is mounted.
3-6
Usage
*2
*3
*4, *5
ON
Setting
Function
ON
Writing disabled for user program memory.
OFF
Writing enabled for user program memory.
ON
The user program is automatically trans-
ferred from the Memory Card when power is
turned ON.
OFF
The user program is not automatically trans-
ferred from the Memory Card when power is
turned ON.
---
---
---
---
ON
Serial port (RS-232C) communications con-
dition: Automatically detect CX-Programmer
(peripheral bus only) baud rate.
OFF
Serial port (RS-232C) communications con-
dition: According to CX-Programmer commu-
nications settings in PLC Setup. (Refer to
Table 1.)
ON
User-defined pin. Turns ON the User DIP
Switch Pin Flag (A395.12).
OFF
User-defined pin. Turns OFF the User DIP
Switch Pin Flag (A395.12).
---
Specifies the simple backup type.
Always
---
OFF.
CJ2 CPU Unit Hardware User's Manual
Default
*1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF