Example Of Recommended Rs-422A/485 Wiring; Connections To The Cpu Unit - Omron CJ2 CPU UNIT User Manual

Cj2 cpu unit hardware
Hide thumbs Also See for CJ2 CPU UNIT:
Table of Contents

Advertisement

Appendices

Connections to the CPU Unit

• Always turn OFF the power supply to the PLC before connecting or disconnecting communica-
tions cables.
• Tighten the communications connector attachment screws to 0.4 N·m.

Example of Recommended RS-422A/485 Wiring

We recommend using the following wiring for RS-422A/485 to ensure transmission quality.
1
Use shielded twisted-pair cable for communications cables.
• Recommended RS-422A/485 Cable
CO-HC-ESV-3P × 7/0.2
2
Connect the shield on the communications cable to the FG terminal on the RS-422A/485 Option
Board. Also, ground the protective earth (GR) terminal on the CPU Unit to a resistance of 100 Ω
or less.
Precautions for Correct Use
Precautions for Correct Use
Connect the shield on the communications cable to the FG terminal on the RS-422A/485 Option
Board. Do not connect it on the other end of the cable. If you ground both ends, a difference in
ground potential may damage the equipment.
A-136
Model
Hirakawa Hewtech Corp.
Manufacturer
CJ2 CPU Unit Hardware User's Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents