Omron NXR Series User Manual page 341

Environment-resistive remote terminal
Hide thumbs Also See for NXR Series:
Table of Contents

Advertisement

Additional Information
• If IO-Link devices are connected to the IO-Link master, you can connect the Sysmac Studio
online and register the IO-Link devices that are actually connected to the IO-Link master. To
use this function, right-click in the device registration area and select Compare and Get
Actual IO-Link Device Information.
• If IO-Link devices are connected to the IO-Link master, you can connect the tool online and
get the serial numbers of the IO-Link devices. To use this function, right-click in the device
registration area and select Get Serial Numbers of All IO-Link Devices.
• If the IO-Link device to register is not displayed in the Toolbox, you need to install its IODD
file. To install an IODD file, right-click in the device registration area and select Install IODD
File.
2
Select the port in the device registration area and edit the parameters displayed in the IO-Link
port setting area.
Precautions for Correct Use
You cannot edit the parameters in the online state.
3
Click the OK button at the lower right of the IO-Link Master Simple Settings tab page. The fol-
lowing dialog box is displayed.
Confirm the displayed message and click the OK button.
This completes the parameter setting and I/O data size editing procedure for the IO-Link mas-
ter.
NXR-series IO-Link Master Unit for EtherCAT User's Manual (W640)
Appendices
A
A-61