7 Setting Up IO-Link Master Unit
PDO
Index
Object name
type
(hex)
1B03
Port5_6 I/O Port
Error Status Infor-
mation
1B04
Port7_8 I/O Port
Error Status Infor-
mation
1B05
Digital Input Data
Set
1BFE
New Messages
Available Informa-
tion
1BFF
Sysmac Error Sta-
tus Information
The following table shows the PDO entries corresponding to these PDO mapping objects.
The PDO entry type that can be registered to the PDO mapping object is fixed. Different type of PDO
entry cannot be registered.
PDO mapping object
PDO
Index
Object name
type
(hex)
RxPDO
1600
Port1 IO-Link Output Data
Indexes: 1601 to 1606
1607
Port8 IO-Link Output Data
1700
Digtal Output Data Set
TxPDO
1A00
Port1 IO-Link Input Data
Indexes: 1A01 to 1A06
1A07
Port8 IO-Link Input Data
1B00
I/O Port Status Information
1B01
Port1_2 I/O Port Error Sta-
tus Information
1B02
Port3_4 I/O Port Error Sta-
tus Information
1B03
Port5_6 I/O Port Error Sta-
tus Information
1B04
Port7_8 I/O Port Error Sta-
tus Information
1B05
Digital Input Data Set
1BFE
New Messages Available In-
formation
1BFF
Sysmac Error Status Infor-
mation
7-8
PDO mapping object
Description
Indicates the error status of ports 5 and
6 on the IO-Link Master Unit.
Indicates the error status of ports 7 and
8 on the IO-Link Master Unit.
Indicates the Digital Input Data Set from
ports 1 to 8 on the IO-Link Master Unit
to the EtherCAT master.
Indicates the new messages available.
This notification indicates the update of
the error log.
Indicates the Sysmac error status.
Index
(hex)
7000
Port1 Output Data
7070
Port8 Output Data
3100
Digital Output Data
6000
Port1 Input Data
6070
Port8 Input Data
3000
I/O Port Status
3001
Port1_2 I/O Port Error
Status
3002
Port3_4 I/O Port Error
Status
3003
Port5_6 I/O Port Error
Status
3004
Port7_8 I/O Port Error
Status
3005
Digital Input Data
10F3
Diagnosis History
Subindex 04 hex:
New Messages Available
2002
Sysmac Error
Subindex 01 hex:
Sysmac Error Status
Selection of PDO
mapping object
Selec-
tion
Possible
Possible
Possible
Possible
Possible
PDO entry
Object name
PDO Entries Assigned to Port
Data on page 7-9
PDO Entries Assigned to Port
Data on page 7-9
PDO Entry Assigned to Digital Output Data Set on
page 7-9
PDO Entries Assigned to Port
ta on page 7-11
PDO Entries Assigned to Port
ta on page 7-11
PDO Entry Assigned to I/O Port Status Information
on page 7-12
PDO Entry Assigned to Port1_2 I/O Port Error Sta-
tus Information on page 7-13
PDO Entry Assigned to Port3_4 I/O Port Error Sta-
tus Information on page 7-15
PDO Entry Assigned to Port5_6 I/O Port Error Sta-
tus Information on page 7-16
PDO Entry Assigned to Port7_8 I/O Port Error Sta-
tus Information on page 7-16
PDO Entry Assigned to Digital Input Data Set on
page 7-16
PDO Entry Assigned to New Messages Available
Information on page 7-19
PDO Entry Assigned to Sysmac Error Status Infor-
mation on page 7-20
NXR-series IO-Link Master Unit for EtherCAT User's Manual (W640)
Change of PDO entry
De-
Default
Editing
fault
entries
Selected
Not pos-
1
sible
Selected
Not pos-
1
sible
Selected
Not pos-
1
sible
Selected
Not pos-
2
sible
Selected
Not pos-
1
sible
Reference
£ IO-Link Output
£ IO-Link Output
£ IO-Link Input Da-
£ IO-Link Input Da-
Maxi-
mum
entries
1
1
1
2
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxr-ilm08c-ect

Table of Contents