This object specifies the index number of the object held by the IO-Link device.
• Subindex
This object specifies the subindex number of the object held by the IO-Link device.
• Length
This object specifies the size of the data to be written when writing. The unit is bytes.
• Data
This object specifies the data to be written when writing.
• Error Code
This object indicates the error code when the status value of subindex 02 hex is 04 hex or 05 hex.
The meanings of the error codes are as follows. When the value of status is 02 hex, the meaning is
normal end, and the value of error code is 0000 hex.
Status
value
04 hex
4806 hex
4807 hex
4808 hex
05 hex
• Timeout
This object is the time that the IO-Link Master Unit monitors a response from an IO-Link device. The
unit is ms. The monitoring time is an integer number of seconds obtained by rounding up the less-
than-second part (lower 3 digits in decimal notation) of the set value to the nearest second. When
0000 hex is specified, the monitoring time is 2 s.
• Sequence No
This object specifies the sequence number of the message to be sent.
A-54
Error code value
The port communications set-
ting is not IO-Link Mode.
There is no IO-Link device.
The I/O power is OFF.
Timeout has occurred.
An IO-Link Communications
Module Processing Error oc-
curs.
An IO-Link Communications
Error occurs.
A Device Configuration Verifi-
cation Error occurs.
Refer to Table C.1 Error Types
Upper 1 byte
Error code defined in
in Annex C of the IO-Link
Interface and System
the IO-Link standard
Specification Version 1.1.2 for
Lower 1 byte
details on the meanings of the
Additional code de-
error codes.
fined in the IO-Link
standard
Error code meaning
NXR-series IO-Link Master Unit for EtherCAT User's Manual (W640)
Correction
Set the port communications setting
to IO-Link Mode.
Connect an IO-Link device.
Turn ON the I/O power.
Change the timeout setting.
Refer to the Sysmac event code and
take the corresponding measure.
Refer to the 11-4-3 Error Table on
page 11-16 for details on the Sys-
mac event codes.
Refer to the instruction manuals for
the connected IO-Link devices and
take the corresponding measure.