Troubleshooting
WARNING/ALARM 9, Inverter overloaded
The frequency converter is about to cut out because of an
overload (too high current for too long). The counter for
electronic, thermal inverter protection gives a warning at
90% and trips at 100%, while giving an alarm. The
frequency converter cannot be reset until the counter is
below 90%.
The fault is that the frequency converter is overloaded by
more than 100% for too long.
NOTICE
See the derating section in the Design Guide for more
details, if a high switching frequency is required.
WARNING/ALARM 10, Motor overload temperature
According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the frequency converter
gives a warning or an alarm when the counter reaches
100% in 1-90 Motor Thermal Protection. The fault is that the
motor is overloaded by more than 100% for too long.
CAUTION
Live Electrical Components!
Troubleshooting:
Check if motor is over heating.
If the motor is mechanically overloaded
That the motor 1-24 Motor Current is set correctly.
Motor data in parameters 1-20 through 1-25 are
set correctly.
Run AMA in 1-29 Automatic Motor Adaption (AMA).
WARNING/ALARM 11, Motor thermistor over temp
CAUTION
Disconnect power before proceeding.
WARNING/ALARM 13, Over current
The inverter peak current limit is exceeded. The warning
lasts about 1.5 s, then the frequency converter trips and
issues an alarm.
Troubleshooting:
This fault may be caused by shock loading or fast
acceleration with high inertia loads.
Turn off the frequency converter. Check if the
motor shaft can be turned.
Check that the motor size matches the frequency
converter.
Incorrect motor data in parameters 1-20 through
1-25.
ALARM 14, Earth (ground) fault
There is a discharge from the output phases to earth,
either in the cable between the frequency converter and
the motor or in the motor itself.
TR150 Programming Guide
CAUTION
Disconnect power before proceeding.
Troubleshooting:
ALARM 16, Short circuit
There is short-circuiting in the motor or on the motor
terminals.
CAUTION
Disconnect power before proceeding.
Turn off the frequency converter and remove the short-
circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the frequency converter.
The warning is only active when 8-04 Control Timeout
Function is NOT set to OFF.
If 8-04 Control Timeout Function is set to Stop and Trip, a
warning appears and the frequency converter ramps down
until it trips, while giving an alarm.
WARNING
Live Electrical Components!
Troubleshooting:
WARNING 24, Fan fault
The fan warning function is an extra protection function
that checks if the fan is running/mounted. The fan warning
can be disabled in 14-53 Fan Monitor ([0] Disabled).
Troubleshooting:
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
BAS-SVP16A-EN - Rev. 2013-09-05
Turn off the frequency converter and remove the
earth fault.
Measure the resistance to ground of the motor
leads and the motor with a megohmmeter to
check for earth faults in the motor.
Check connections on the serial communication
cable.
Increase 8-03 Control Timeout Time
Check operation of the communication
equipment.
Verify proper installation based on EMC
requirements.
Check fan resistance.