Parameters
3.4.4 3-5* Ramp 2
Selecting ramp parameters, see parameter group 3-4*
Ramp 1.
3-51 Ramp 2 Ramp Up Time
Range:
Function:
Size
[0.05
Enter acceleration time from 0 Hz to
related
- 3600
1-23 Motor Frequency if Asynchronous
*
s]
motor is selected. Enter acceleration time
from 0 RPM to 1-25 Motor Nominal Speed if
PM motor is selected. Select a ramp-down
time such that the output current does not
exceed the current limit in 4-18 Current
Limit during ramping. See ramp-down time
in 3-52 Ramp 2 Ramp Down Time.
3-52 Ramp 2 Ramp Down Time
Range:
Function:
Size
[0.05
Enter deceleration time from 1-23 Motor
related
- 3600
Frequency to 0 Hz if Asynchronous motor is
*
s]
selected. Enter deceleration time from
1-25 Motor Nominal Speed to 0 RPM if PM
motor is selected. Select a ramp-down time
such that the output current does not
exceed the current limit in 4-18 Current
Limit during ramping. See ramp-up time in
3-51 Ramp 2 Ramp Up Time.
3.4.5 3-8* Other Ramps
3-80 Jog Ramp Time
Range:
Function:
Size
[0.05
Enter the jog ramp time, i.e. the
related
- 3600
acceleration/deceleration time between 0 Hz
*
s]
to 1-23 Motor Frequency. Ensure that the
resultant output current required for the
given jog ramp time does not exceed the
current limit in 4-18 Current Limit. The jog
ramp time starts upon activation of a jog
signal via the control panel, a selected
digital input, or the serial communication
port.
3-81 Quick Stop Ramp Time
Range:
Function:
Size
[0.05 -
Enter the quick stop ramp time from the
related
3600 s]
1-23 Motor Frequency to 0 Hz. During
*
ramping, no over-voltage may arise in the
inverter, nor may the generated current
exceed the limit in 4-18 Current Limit is
activated by means of a signal on a
selected digital input or via the serial
communication port.
TR150 Programming Guide
BAS-SVP16A-EN - Rev. 2013-09-05