Parameters
13-02 Stop Event
Option:
[34]
Digital input DI19
[35]
Digital input DI27
3
3
[36]
Digital input DI29
[39]
Start command
[40]
Drive stopped
*
[42]
Auto Reset Trip
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[83]
Broken Belt
13-03 Reset SLC
Option:
[0]
Do not reset
*
SLC
[1]
Reset SLC
58
TR150 Programming Guide
Function:
Use the value of DI27 in the logic rule
(High = TRUE).
Use the value of DI29 in the logic rule
(High = TRUE).
This event is TRUE if the frequency
converter is started by any means
(either via digital input, fieldbus or
other).
This event is TRUE if the frequency
converter is stopped or coasted by
any means (either via digital input,
fieldbus or other).
This event is TRUE if the frequency
converter is tripped (but not trip-
locked) and an Automatic Reset is
issued.
Use the result of comparator 4 in the
logic rule.
Use the result of comparator 5 in the
logic rule.
Use the result of logic rule 4 in the
logic rule.
Use the result of logic rule 5 in the
logic rule.
Use the result of timer 3 in the logic
rule.
Use the result of timer 4 in the logic
rule.
Use the result of timer 5 in the logic
rule.
Use the result of timer 6 in the logic
rule.
Use the result of timer 7 in the logic
rule.
A broken belt condition has been
detected. This function must be
enabled in 22-60 Broken Belt Function.
Function:
Retains programmed settings in all group 13
parameters (13-** Smart Logic).
Resets all group 13 parameters (13-** Smart
Logic) to default settings.
3.9.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Illustration 3.14 Comparators
In addition, there are digital values that are compared to
fixed time values. See explanation in 13-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [6]
Option:
[0]
Disabled
*
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor Current
[6]
Motor power
[7]
Motor voltage
[12] Analog input AI53
[13] Analog input AI54
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
Array [6]
Option:
[0]
Less Than (<)
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
Select the variable to be monitored by
the comparator.
Function:
Select [0] < for the result of the evaluation
to be TRUE, when the variable selected in
13-10 Comparator Operand is smaller than
the fixed value in 13-12 Comparator Value.
The result is FALSE, if the variable selected
in 13-10 Comparator Operand is greater
than the fixed value in 13-12 Comparator
Value.