3.10.5 14-5* Environment
These parameters help the frequency converter to operate
under special environmental conditions.
14-50 RFI Filter
3
3
Option: Function:
[0]
Off Select [0] Off only if the frequency converter is fed by
an isolated mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
On
Select [1] On to ensure that the frequency converter
*
complies with EMC standards.
14-51 DC-Link Voltage Compensation
Option:
[0]
Off
[1]
On
*
14-52 Fan Control
Option:
[0]
Auto
*
[4]
Auto Low Temp
Env.
14-53 Fan Monitor
Option:
[0]
Disabled
[1]
Warning
*
[2]
Trip
14-55 Output Filter
Option:
[0]
No Filter
*
[1]
Sine-Wave Filter
[3]
Sine-Wave Filter with
Feedback
14-63 Min Switch Frequency
Set the minimum switch frequency allowed by the output filter.
Option:
[2]
*
[3]
[4]
[5]
[6]
66
TR150 Programming Guide
Function:
Disables DC Link Compensation.
Enables DC Link Compensation.
Function:
Only valid for the following frequency
converters: 380-480 V, 30-90 kW.
Function:
Select which reaction the frequency converter
should take in case a fan fault is detected. (Only
valid for some frequency converter sizes.)
Function:
Select whether an output
filter is present.
Function:
2.0 kHz
3.0 kHz
4.0 kHz
5.0 kHz
6.0 kHz
14-63 Min Switch Frequency
Set the minimum switch frequency allowed by the output filter.
Option:
[7]
[8]
[9]
[10]
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
8.0 kHz
10.0 kHz
12.0kHz
16.0kHz