20-94 PI Integral Time
Range:
20 s
[0.10 -
*
9999 s]
3
3
20-97 PI Feed Forward Factor
Range:
0 %
*
74
TR150 Programming Guide
Function:
Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Function:
[0 - 400 %]
BAS-SVP16A-EN - Rev. 2013-09-05