How to Program
Parameter
Range
1-24 Motor Current
0.01-10000.00 A
1-25 Motor Nominal
100.0-9999.0 RPM
Speed
1-26 Motor Cont. Rated
0.1-1000.0
Torque
1-29 Automatic Motor
See 1-29 Automatic Motor
Adaption (AMA)
Adaption (AMA)
1-30 Stator Resistance
0.000-99.990
(Rs)
1-37 d-axis Inductance
0-1000
(Ld)
1-39 Motor Poles
2-100
1-40 Back EMF at 1000
10-9000
RPM
1-73 Flying Start
1-73 Flying Start
[0] Disabled
[1] Enabled
3-02 Minimum Reference -4999-4999
3-03 Maximum Reference -4999-4999
3-41 Ramp 1 Ramp Up
0.05-3600.0 s
Time
3-42 Ramp 1 Ramp
0.05-3600.0 s
Down Time
4-12 Motor Speed Low
0.0-400 Hz
Limit [Hz]
4-14 Motor Speed High
0.0-400 Hz
Limit [Hz]
4-19 Max Output
0-400
Frequency
5-40 Function Relay [0]
See 5-40 Function Relay
Function relay
5-40 Function Relay [1]
See 5-40 Function Relay
Function relay
6-10 Terminal 53 Low
0-10 V
Voltage
TR150 Programming Guide
Default
Size related
Size related
Size related
Off
Size related
Size related
4
Size related
0
0
50
Size related
Size related
0 Hz
65 Hz
Size related
Alarm
Drive running
0.07 V
BAS-SVP16A-EN - Rev. 2013-09-05
Function
Enter motor current from nameplate data
Enter motor nominal speed from nameplate data
This parameter is available only when 1-10 Motor
Construction Design is set to [1] PM, non-salient
SPM.
NOTICE
Changing this parameter affects
settings of other parameters
Performing an AMA optimises motor performance
Set the stator resistance value
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
Enter the number of motor poles
Line-Line RMS back EMF voltage at 1000 RPM
When PM is selected, Flying Start is enabled and
can not disable
Select [1] Enable to enable the frequency converter
to catch a motor spinning due to mains drop-out.
Select [0] Disable if this function is not required.
When is enabled 1-71 Start Delay and 1-72 Start
Function have no function. is active in VVC
mode only
The minimum reference is the lowest value
obtainable by summing all references
The maximum reference is the lowest obtainable
by summing all references
Ramp up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected; ramp up
time from 0 to 1-25 Motor Nominal Speed if PM
motor is selected
Ramp down time from rated 1-23 Motor Frequency
to 0 if Asynchron motor is selected; ramp down
time from 1-25 Motor Nominal Speed to 0 if PM
motor is selected
Enter the minimum limit for low speed
Enter the maximum limit for high speed
Enter the maximum output frequency value
Select the function to control output relay 1
Select the function to control output relay 2
Enter the voltage that corresponds to the low
reference value
2
2
plus
13