Parameters
6-16 Terminal 53 Filter Time Constant
Range:
3
3
6-19 Terminal 53 mode
Option:
[0]
Current mode
[1]
Voltage mode
*
3.7.3 6-2* Analog Input 54
Parameters for configuring the scaling and limits for
analog input 54 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
0.07 V
[0 -
*
10 V]
6-21 Terminal 54 High Voltage
Range:
10 V
[0 - 10 V] Enter the voltage (V) that corresponds to the
*
6-22 Terminal 54 Low Current
Range:
4 mA
[0 -
*
20 mA]
6-23 Terminal 54 High Current
Range:
20 mA
[0 - 20 mA]
*
20.00 mA
[par. 6-22-20.00
*
mA]
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0
[-4999 -
*
4999 ]
48
TR150 Programming Guide
Function:
but also increases the time delay through the
filter.
Function:
Select if terminal 53 is used for current- or
voltage input.
Function:
Enter the voltage (V) that corresponds to the
low reference value (set in 6-24 Terminal 54 Low
Ref./Feedb. Value). The value must be set at >1
V to activate 6-01 Live Zero Timeout Function.
Function:
high reference value (set in 6-25 Terminal 54
High Ref./Feedb. Value).
Function:
Enter the low current value. This reference
signal should correspond to the low reference/
feedback value, set in 6-24 Terminal 54 Low Ref./
Feedb. Value. The value must be set at >2 mA to
activate the Live Zero Timeout Function in
6-01 Live Zero Timeout Function.
Function:
Enter the high current value
corresponding to the high
reference/feedback value set in
6-25 Terminal 54 High Ref./Feedb.
Value.
Function:
Enter the reference or feedback value that
corresponds to the voltage or current set in
6-21 Terminal 54 High Voltage/6-22 Terminal 54
Low Current.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Size related
*
6-26 Terminal 54 Filter Time Constant
Range:
0.01 s
[0.01 -
*
10 s]
6-29 Terminal 54 mode
Option:
[0]
Current mode
[1]
Voltage mode
*
3.7.4 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for
analog/digital output Terminal 45. Analog outputs are
current outputs: 0/4-20 mA. Resolution on analog output is
12 bit. Analog output terminals can also be setup as digital
output.
6-70 Terminal 45 Mode
Option:
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-71 Terminal 45 Analog Output
Option:
[0]
No operation
*
[100] Output frequency 0-400 Hz
[101] Reference
[102] Feedback
[103] Motor Current
[106] Power
[139] Bus Control
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
[-4999 -
Enter the reference or feedback value
4999 ]
that corresponds to the voltage or
current set in 6-21 Terminal 54 High
Voltage/6-23 Terminal 54 High Current.
Function:
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 54. A
high time constant value improves dampening
but also increases the time delay through the
filter.
Function:
Select if terminal 54 is used for current- or
voltage input.
Function:
Set terminal 45 to act as analog output or
as digital output.
Function:
Select the function of Terminal 45 as an
analog current output. See also
6-70 Terminal 45 Mode.
Min
- Max
Ref.
Ref.
Min
- Max
FB
FB
0-I
max
0-P
nom
0-100%