Parameters
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[4]
Standby / no
Frequency converter is ready for
warning
operation. No start or stop command is
given. No warnings are present.
[5]
Drive running
Motor is running.
[6]
Running / no
Motor runs, and no warning are present.
warning
[7]
Run in range/no
Motor runs within programmed current
warning
ranges, see 4-50 Warning Current Low
and 4-51 Warning Current High. No
warnings are present.
[8]
Run on ref/no
Motor runs at reference speed and with
warning
no warnings.
[9]
Alarm
An alarm activates output.
[10]
Alarm or
An alarm or warning activates output.
warning
[12]
Out of current
Motor current is outside range set in
range
4-50 Warning Current Low and
4-51 Warning Current High.
[13]
Below current,
Motor current is lower than set in
low
4-50 Warning Current Low.
[14]
Above current,
Motor current is higher than set in
high
4-51 Warning Current High.
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below feedback,
low
[20]
Above feedback,
high
[21]
Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in motor,
frequency converter or thermistor.
[22]
Ready, no
Frequency converter is ready for
thermal warning
operation and no over-temperature
warning is present.
[23]
Remote, ready,
Frequency converter is ready for
no thermal
operation in Auto mode, and no over-
warning
temperature warning is present.
[24]
Ready, Voltage
Frequency converter is ready for
OK
operation and mains voltage is within
specified voltage range.
[25]
Reverse
Motor runs/is ready to run clockwise
when logic = 0 and counter clockwise
TR150 Programming Guide
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
[26]
Bus OK
[35]
External
Interlock
[36]
Control word bit
11
[37]
Control word bit
12
[41]
Below reference,
low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
when logic = 1. Output changes as soon
as reversing signal is applied.
Active communication (no time-out) via
serial communication port.
See digital input.
Bit 11 in control word controls relay.
Bit 12 in control word controls relay.
See parameter group 13-1* Comparators.
If Comparator 0 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
See parameter group 13-1* Comparators.
If Comparator 2 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
See parameter group 13-1* Comparators.
If Comparator 2 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
See parameter group 13-1* Comparators.
If Comparator 3 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
See parameter group 13-1* Comparators.
If Comparator 4 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
See parameter group 13-1* Comparators.
If Comparator 5 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Logic Rules. If
Logic Rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
See parameter group 13-4* Logic Rules. If
Logic Rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it islow.