Trane TR150 Programming Manual page 66

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Parameters
14-20 Reset Mode
Option:
Function:
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
Select [13] Infinite Automatic Reset for
continuous resetting after tripping.
NOTICE
The motor may start without warning. If the specified
number of AUTOMATIC RESETs is reached within 10
minutes, the frequency converter enters Manual reset [0]
mode. After the Manual reset is performed, the setting
of 14-20 Reset Mode reverts to the original selection. If
the number of automatic resets is not reached within 10
minutes, or when a Manual reset is performed, the
internal AUTOMATIC RESET counter returns to zero.
Note
Automatic reset will also be active for resetting safe torque
off function.
Note
The setting in 14-20 Reset Mode is disregarded in case of
Fire Mode being active (see parameter group 24-0*, Fire
Mode).
14-21 Automatic Restart Time
Range:
Function:
10 s
[0 - 600
Enter the time interval from trip to start of the
*
s]
automatic reset function. This parameter is
active when 14-20 Reset Mode is set to [1] - [13]
Automatic reset.
14-22 Operation Mode
Option:
Function:
Select [2] Initialisation to reset all parameter
values to default.
[0]
Normal
Select [0] Normal operation for normal
*
operation
operation of the frequency converter with the
motor in the selected application.
[2]
Initiali-
Select [2] Initialisation to reset all parameter
sation
values to default settings, except for
15-03 Power Up's, 15-04 Over Temp's and
15-05 Over Volt's. The frequency converter is
reset during the next power-up.
14-22 Operation Mode also reverts to the
default setting [0] Normal operation.
TR150 Programming Guide
14-23 Typecode Setting
Range:
0
[0 - 255 ] Typecode re-writing. Use this parameter to set
*
14-27 Action At Inverter Fault
Option:
[0]
Trip
[1]
Warning
*
14-28 Production Settings
Option:
[0]
*
[1]
[3]
14-29 Service Code
Range:
0
[0 - 0x7FFFFFFF ]
*
3.10.4 14-4* Energy Optimising
Parameters for adjusting the energy optimisation level in
both Variable Torque (VT) and Automatic Energy Optimi-
sation (AEO) mode.
Automatic Energy Optimisation is only active if 1-03 Torque
Characteristics, is set for [3] Auto Energy Optim.
14-40 VT Level
Range:
90 %
*
90%
*
14-41 AEO Minimum Magnetisation
Range:
66 %
*
66%
*
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
the typecode matching the specific frequency
converter.
Function:
Select how the frequency converter should react
at inverter fault. Action At Inverter Fault
Function:
No action
Production use only.
Service reset
Software Reset
Function:
Service use only.
Function:
NOTICE
[40 - 90 %]
This parameter cannot be adjusted
while the motor is running.
Enter the level of motor magnetisation at
low speed. Selection of a low value reduces
energy loss in the motor, but also reduces
load capability.
[40-90%]
Function:
[40 - 75 %] Enter the minimum allowable magnetisation
for AEO. Selection of a low value reduces
energy loss in the motor, but can also
reduce resistance to sudden load changes.
[40-75%]
3
3